Finding · as stated by the study, recorded by Coridum · status verified-machine
Finding F-0413
“The use of the dynamic window ratios, from 0.23% to 2.16%, modified according to the measured carbon dioxide concentration, can partially maintain the carbon dioxide below the required limits for ASHRAE 62.1, Hygiene Measures Against COVID‐19 and UNE‐EN 16798 between 48.28% to 74.14% of the time.”
Structure
- Factor
- Carbon dioxide (CO₂)
- Intervention
- Natural ventilation
- Population
- school pupils
- Setting
- classroom, ES
- Study design
- validation of a dynamic natural ventilation protocol in a school classroom in Huelva (subtropical climate, winter): CO2-driven window opening ratios first simulated, then monitored on three non-consecutive days in winter 2021 with 21 occupants, share of time below the CO2 limits of ASHRAE 62.1, UNE-EN 16798, the Spanish COVID-19 hygiene protocol (800 ppm) and RITE (500 ppm) (class 4)
- Effect
- share-below 48.28
- Averaging time
- share of monitored time over three school days
- Caveat
- the sentence gives a range across days; the two ends are recorded as two rows