Finding · as stated by the study, recorded by Coridum · status verified-machine

Finding F-0482

“In the first part of the measurements (3–8 October), when the door was opened to maintain the CO2 concentration below 1000 ppm, the 222 Rn concentration also remained below 100 Bq m−3 for most of the time (range 5–149 Bq m−3 and average 46 ± 23 Bq m−3 ).”

Dovjak et al. Analysis of Ventilation Efficiency as Simultaneous Control of Radon and Carbon Dioxide Levels in Indoor Air Applying Transient Modelling (2022). Page 9. CKB 0342

Structure

Factor
Radon
Intervention
Natural ventilation
Population
apartment occupants
Setting
apartment, SI
Study design
continuous measurement of radon-222 and CO2 with meteorological parameters in one occupied apartment (about 27 m2) in Ljubljana, Slovenia, 3-15 October, under recorded ventilation schedules (frequent, poor, none), followed by CONTAM 3.4 transient simulations of design ventilation rates (class 4)
Effect
mean 46
Averaging time
average over 3-8 October, door opened to keep CO2 below 1000 ppm
Caveat
the ± value is not named in the sentence

A Finding records what one published document states, verbatim and with its page. It is not a conclusion of Coridum; see the Claims that build on it.