Infiltration
Also: air leakage, infiltration factor
Uncontrolled leakage of outdoor air into a building through cracks, joints and gaps, driven by wind and temperature difference. It ventilates leaky old buildings by accident and lets outdoor pollutants — and radon from the ground — in.
Why it matters indoors
Infiltration is ventilation nobody chose. In old buildings it can exceed 1 air change per hour and keep CO₂ low at the cost of heat; in airtight new buildings it falls below 0.1 and mechanical ventilation becomes necessary. It also sets how much outdoor particulate matter and nitrogen dioxide reach the interior (the infiltration factor, typically 0.3–0.8 for PM₂.₅) and, through the floor, how much radon enters. Blower-door tests measure airtightness.