Finding · as stated by the study, recorded by Coridum · status verified-machine

Finding F-0485

“Outdoor air required inside the surgery room was 167 l/s, while the actual ventilation was 51 l/s.”

Particle and Carbon Dioxide Concentration Levels in a Surgical Room Conditioned with a Window/Wall (2020). International journal of environmental research and public health. Page 6. CKB 7696

Structure

Factor
Air exchange rate (air changes per hour)
Intervention
Air conditioning
Population
surgical staff and patients
Setting
operating room, BR
Study design
measurement of particle number concentration (0.3-10 μm) and CO2 in one surgical room with a window/wall air-conditioning system and the adjacent corridor in Brazil during a single surgery and two subsequent surgeries, with outdoor air ventilation calculated from CO2 and compared with the requirement (class 4)
Effect
other 51
Caveat
outdoor airflow in l/s filed under air-exchange-rate; both values are calculated from the CO2 balance, the requirement is not a measurement

A Finding records what one published document states, verbatim and with its page. It is not a conclusion of Coridum; see the Claims that build on it.